Direct Gas-Fired MUA: We install and service TSSA-approved MUA units that heat freezing sub-zero outdoor air to a comfortable 20°C before bringing it into your kitchen.

Air Balancing: Maintaining an 80%-90% airflow replenishment to keep a perfect indoor pressure.
makeup01

Technical Features & Selection

1)CFM Matching :According to NFPA 96 and Ontario Building Code (OBC), the make-up air volume typically needs to reach 80% to 90% of the exhaust air volume (to maintain a slight negative pressure in the kitchen and prevent cooking fumes from entering the lobby).

2)Interlock System( ):Emphasis is placed on coordinated control. When the exhaust fan is turned on, the MUA automatically starts; when the exhaust fan is turned off, the MUA automatically turns off.
3)VFD - Variable Frequency Drive :It supports automatic adjustment of air volume based on the intensity of cooking in the kitchen, helping the owner save electricity and gas.